Skip to content

Supported Protocols

CONNECT uses one protocol per interface, and several interfaces can run in one gateway. Each protocol has its own page with its connection requirements, limitations and a section Create or import signals.

Choosing an interface type in the CONNECT panel

Every interface follows the same path from controller to client.

Controllers, interfaces, signals and clients Controllers and devices such as PLCs, robots, brokers and simulators each connect to CONNECT through one interface per protocol. Several interfaces run in one gateway. Their values become ordinary signals in the gateway, which the viewer and your own tools read through the same signal channel. Values from the PLC reach the viewer; values written by the viewer reach the controller only when Allow web to PLC is switched on for that interface. PLCS7, ADS, Modbus, OPC UA Robot controllerFANUC, UR, KUKA, ... Broker, drive, toolMQTT, UDP, REST SimulatorPLCSIM, ROS 2, SHM CONNECT gateway Interfacesone protocolper interfaceseveral can runin one gateway Signalsname, type, valuePLCOutput: readby the viewerPLCInput: writtenby the viewer Viewer3D, HMI Your toolsREST, WebSocket writes to the controllerneed Allow web to PLC
Every protocol page in this section describes the left half of this picture: how one interface reaches its controller and turns its data into signals.

The Add Interface dialog offers the following protocol interfaces. FMU co-simulation is offered there too and has its own page: FMU.

Interface typeTarget systemAddressSignals found by
MQTT BrokerAny MQTT broker; Siemens process image; flat JSON (SEW MOVI-C)TopicBrowse, tag-table or symbol-table import
REST API (API bridge)Cloud and REST services, such as condition monitoring or CMMSAllowed API pathNo signals; data displayed by a project plugin
OPC UAAny OPC UA serverNodeIdBrowse
Siemens S7S7-300/400/1200/1500, PLCSIM Advanced over S7commDB1.DBX0.0Manual, or browse a TIA .sdf symbol table
Siemens PLCSIM Advanced (native API)PLCSIM Advanced on this machine or on another PC, through the Siemens simulation APITag nameBrowse
Beckhoff TwinCAT ADSTwinCAT 2 and 3, CX, soft-PLCSymbolBrowse
Modbus TCP ClientDrives, sensors, Modbus gatewaysHR40001Manual
Modbus TCP ServerA PLC or SCADA connecting to CONNECTHR0Manual
EtherNet/IPAllen-Bradley ControlLogix, CompactLogix, Micro800, OmronTagBrowse
B&R PVI (ANSL/INA2000)B&R controllers and ArSim, through the B&R PVI installation on this PCgCounter, Prog1:localCnt, stData.SpeedBrowse
Mitsubishi MELSEC (MC 3E)MELSEC iQ-R, Q, L and iQ-F over MC protocol (SLMP 3E binary)D100, M0, D200:floatManual, or browse a GX Works3 CSV export
UDP (binary telegram)A PLC, SCADA system or your own tool exchanging fixed binary telegrams0:BOOL, 4:INT, 8:REALManual, or browse a CSV symbol table
SEW MOVI-C (UDP)SEW MOVI-C controller or simulation using the Unity SEW UDP layout0:BOOL, 4:INT, 8:REALSEW symbol-table import in the browser, or browse a CSV symbol table
CODESYS NVL (UDP)CODESYS-based controllers (CODESYS Control, ctrlX PLC, WAGO, KEB) exchanging Network Variable Lists1/0:BOOL, 1/2:INTImport a .gvl file
ART DTrack (tracking)ART head and Flystick tracking over UDPGenerated pose and input signalsGenerated from configured counts
OptiTrack NatNet (tracking)OptiTrack Motive rigid bodies over UDPGenerated pose signalsGenerated in BodyIds order
Bosch Rexroth ctrlXctrlX CORE through the bridge snapNode pathBrowse
Bosch Rexroth ctrlX (Data Layer)ctrlX CORE natively, no snap neededNode pathBrowse
Keba Kemro XKeba controllersVariableBrowse
WebSocket Realtime (realvirtual v2)realvirtual for Unity, another CONNECT or the ctrlX bridge — CONNECT as server or clientSignal nameBrowse (the signals the peer offers)
Festo AX (PLCnext)Festo AX, Phoenix Contact PLCnextVariableBrowse
FANUC (RoboGuide / Robot-IF)FANUC controller or RoboGuidedo4, di1Manual
Denso (b-CAP / WinCaps VRC)Denso RC8/RC9, WinCaps VRCIO104, P10, axis1Manual
Yaskawa Motoman (HSES)Yaskawa Motoman controllers with High Speed Ethernet Serveraxis1, io:1001.0, status:servo, var:R0Manual
Stäubli CS8/CS9 (SOAP)Stäubli CS8 and CS9 controllersaxis1, io:<name>, status:runningManual
ROS 2 (rosbridge)ROS 2 through rosbridge, for example Isaac Sim, MoveIt or Nav2/cmd_vel#linear.xBrowse (topics and fields through rosapi)
KUKA OfficeLite (Y200 TCP)KUKA OfficeLite through the OC_Assistant_OfficeLite Y200 serverin1, out1, axis1Manual
KUKA iiQKA / RSI (UDP)KUKA iiQKA VRC or a KUKA controller with RSI Ethernetdigin1, digout1, axis1Manual
Universal Robots (RTDE)URSim or a UR controllerdo0, di0, axis1Manual
igus ReBeL (CRI)igus robot control (iRC) and its simulationaxis1, dout20, cmd:movejointManual
RoboDK (API)A running RoboDK stationaxis1, param:PartCount, prog:runManual
Wandelbots NOVAA Wandelbots NOVA cellaxis1, io:<name>, prog:runBrowse (controller IOs)
ABB RobotStudio (SIMIT SHM)RobotStudio on the same PCSignal nameManual
Shared Memory (SIMIT)SIMIT or a Unity consumer on the same PCSignal nameManual
WINMOD Y200 (Shared Memory)WINMOD on the same PCMB13.6, MI100, MF106Manual, or browse a WINMOD signal list

Browse means the controller can be asked what it offers, so signals are selected rather than typed. For S7, Mitsubishi, UDP and WINMOD the browse reads a symbol file named in the interface settings instead of asking the controller. Manual means the protocol has no browse mechanism and addresses are entered — validated against the same parser the interface uses at connect time.

The Yaskawa Motoman, Stäubli and ROS 2 interfaces are in beta: they are marked with a Beta badge in the Add Interface dialog and have not yet been verified on every controller generation. The Festo AX / PLCnext interface is in beta since CONNECT 1.11, because it now uses a new native implementation without the vendor DLL.

Tracking interfaces generate their signal sets from the interface settings. They do not browse a controller or exchange manually added signals.

Windows only: Festo AX, FANUC, Denso, ABB RobotStudio, Shared Memory (SIMIT), WINMOD Y200, B&R PVI and the native PLCSIM Advanced interface. The Linux build — for example CONNECT on a ctrlX CORE — does not offer them. DTrack and NatNet work on both Windows and Linux.

Supported value types are Boolean, integer and floating point throughout, plus text where the protocol carries it. The per-protocol pages name the exact data types each one accepts.

  • Common concepts — how signals get into an interface, direction, write access, text signals, tracking signals and coordinates

This page used to hold every protocol. Each old section now has its own page; the headings below keep links such as protocols/#ros-2-rosbridge working.

Now at Common concepts.

Now at OPC UA.

Now at Siemens S7.

Now at Siemens PLCSIM Advanced.

Now at Siemens PLCSIM Advanced.

Now at Siemens PLCSIM Advanced.

Now at MQTT.

Now at MQTT.

Now at MQTT.

Now at MQTT.

Now at REST API Bridge.

Now at Beckhoff TwinCAT ADS.

Now at Beckhoff TwinCAT ADS.

Now at Beckhoff TwinCAT ADS.

Now at Modbus TCP.

Now at Modbus TCP.

Now at EtherNet/IP.

Now at B&R PVI.

Now at Mitsubishi MELSEC.

Now at UDP and SEW MOVI-C.

Now at UDP and SEW MOVI-C.

Now at CODESYS NVL.

Now at ART DTrack.

Now at OptiTrack NatNet.

Now at Common concepts.

Now at Bosch Rexroth ctrlX.

Now at Bosch Rexroth ctrlX.

Now at Bosch Rexroth ctrlX.

Now at Keba Kemro X.

Now at WebSocket Realtime.

Now at Festo AX / PLCnext.

Now at FANUC.

Now at Denso.

Now at Yaskawa Motoman.

Now at Stäubli CS8/CS9.

Now at ROS 2 (rosbridge).

Now at ROS 2 (rosbridge).

Now at ROS 2 (rosbridge).

Now at ROS 2 (rosbridge).

Now at ROS 2 (rosbridge).

Now at ROS 2 (rosbridge).

Now at ROS 2 (rosbridge).

Now at ROS 2 (rosbridge).

Now at KUKA OfficeLite.

Now at KUKA iiQKA / RSI.

Now at Universal Robots.

Now at igus ReBeL.

Now at RoboDK.

Now at Wandelbots NOVA.

Now at ABB RobotStudio.

Now at Shared Memory (SIMIT).

Now at WINMOD Y200.